TC failure classifications

High / Low / Negligible per NR/L3/SIG/10047 Mod 03 — determines FMS risk level, response and sign-back requirements.

High

  • SCWO — controlling an auto signal
  • SCWO — controlling a signal working in auto / ARS
  • SCWO — controlling a controlled signal not working in auto / ARS
  • SCWO — controlling a level crossing (except ABCL/AOCL or TMO with driver indication)
  • Showing clear where a TC interrupter is broken
  • TCOD — 'occupied' TC clearing following correct application of TCOD
  • SCWO — route locking maintained yet indication showing clear (USR not timed out) — poster only; the 2026 guidance rates this Low

Low

  • SCWO — indication-only failure, interlocking functioned correctly
  • SCWO — controlling ABCL, AOCL or TMO level crossings only
  • TC operating but drop shunt >0.2Ω below the minimum permissible for that asset

Negligible

  • SCWO — short duration and the interlocking has not responded (under 300 ms)
  • SCWO — under 1 s 'striking out' across a track-section boundary while the abutting forward track is occupied
  • SCWO — under 1 s 'striking in' across a track-section boundary while the abutting rear track is occupied
  • SCWO — reported after protection special working is in place
  • SCWO — line not used for some time and protected by TS11 (rusty rails)

Hazard index

Failure modeRIDDORHazardRatingClass
SCWO — automatic signalYesPotential unsafe wrong-side condition (false clear)H9High
SCWO — signal working in auto / ARSYesPotential unsafe wrong-side condition (false clear)H7High
SCWO — controlled signal not in autoYesPotential unsafe wrong-side condition (false clear)H6High
Showing clear with TC interrupter brokenYesPotential unsafe wrong-side condition (false clear)H4High
TCOD — occupied circuit clearing after a correct TCODYesPotential unsafe wrong-side condition (false clear)H4High
SCWO — controlling a level crossing (except ABCL/AOCL/TMO)YesPotential unsafe wrong-side condition (false clear)H4High
SCWO — route locking maintained, USR not timed outNoLimited / protected wrong-side conditionL2Low
SCWO — ABCL/AOCL/TMO crossing onlyNoLimited / protected wrong-side conditionL2Low
Drop shunt ≥0.2Ω below minimumNoLimited / protected wrong-side conditionL2Low
SCWO — indication-only circuitNoLimited / protected wrong-side conditionL1Low
SCWO — under 300msNoNo credible hazardN0Negligible
SCWO — sequencing controls effective (SSI8003-82)NoNo credible hazardN0Negligible
SCWO — <1s striking out/in at TC boundary with abutting circuit occupiedNoNo credible hazardN0Negligible
SCWO — after TS11 special block imposedNoNo credible hazardN0Negligible
Rusty rails — TS11 arrangementsNoNo credible hazardN0Negligible

Classification per NR/L3/SIG/10047 Mod 03 §10.1 (section 4 of the EM RE(S) Autumn Working Guidance 2026). High classifications are RIDDOR-reportable.

Where RCM has identified railhead contamination effects of any duration and it is positively proved the interlocking did not respond, the event is NOT a wrong-side failure (Appendix A flow chart). Track-section boundary transitions under 1 s with the abutting TC still occupied are Negligible (clause 3.13) but should be actioned as an early warning.

Discrepancy carried into 2026: the 'Classifications of TC failures East Midlands' poster rates 'SCWO — route locking maintained, USR not timed out' as HIGH, whereas section 4 of the 2026 guidance lists it under Low risk (protected, see Appendix A 3.7 & 3.8). Treat as the higher classification until route S&T confirms.